B
16
Manual model IndAC
2.10 Switching on and
checking operation
For all units:
1 Check the following connections:
- power supply;
- cabling between control unit and
units, and between the different
units;
- external control components (if any).
2 Switch the mains supply on.
3 Switch the air curtain on using the control
unit, and check if the air curtain blows
out air.
c
Caution:
If the fans run out of true, the unit may
not be standing or hanging completely
level. Correct this where necessary.
4 Check the direction of rotation of the
fans.
Wrong: the blades go
forward
Correct: the blades go
backward
If necessary, correct the direction of
rotation by interchanging the connections
of two phases from the mains supply.
For water-heated units:
5 Check if the heat exchanger is
connected correctly.
6 Make sure the CH system is turned on.
7 Feel whether the discharged air gets
warm.
8 Vent the heat exchanger, if necessary.
For units with electric heating:
9 Set the isolating switches on all units to
position 1.
10 Switch the air curtain on using the control
unit.
11 Feel if the discharged air gets warm.
Comentarios a estos manuales