Technical data CA
2
S/M/L/XL - 100
The CA
2
air curtain is as a standard suitable for all water ranges from 45/35 °C to 90/70°C.
1
Dependingonthesituationtheoutlettemperaturevariesinallspeedsbetween20°Cand50°Cmax.
2
Basedonalimitedairoutlettemperatureof50°C.
3
Basedonawaterrangeof60/40°C.
Basic data:
•doorwidth : 100cm
•roomtemperature : 20ºC
•airoutlettemperature
1
: speed1-5=35°C
speed6 =40°C
•powersupply :W=230V/E=400V
*Seetableonpage10.
12
CA
2
S-100
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
200 - 240
46/60/58
11.6
262
0.68
0.19
0.85
-
-
51/65/63
10.0
-
-
0.19
0.85
10.5
16.0
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
420
2.1
27
585
2.9
35
675
3.4
38
875
4.4
43
1015
5.1
47
1155
7.7
50
CA
2
M-100
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
220 - 280
52/66/64
15.8
321
1.00
0.27
1.24
-
-
55/69/67
13.3
-
-
0.27
1.24
14.0
22.7
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
490
2.5
26
730
3.7
36
880
4.4
41
1195
6.0
47
1425
7.2
50
1575
10.5
53
CA
2
L-100
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
250 - 330
64/82/80
33.0
586
1.18
0.67
3.03
-
-
69/87/85
23.3
-
-
0.67
3.03
24.5
37.9
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
1145
5.7
37
1510
7.6
42
1890
9.5
46
2430
12.2
52
2865
14.4
56
3285
22.0
58
CA
2
XL-100
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
300 - 380
68/86/84
40.0
653
1.44
1.11
5.02
-
-
73/91/89
23.3
-
-
1.11
5.02
24.5
39.7
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
1370
6.9
43
1815
9.1
47
2295
11.5
51
2975
14.9
56
3535
17.7
60
3980
26.6
63
Comentarios a estos manuales