Biddle CA2 Manual de usuario Pagina 14

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 20
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 13
Technical data CA
2
S/M/L/XL - 200
14
Basic data:
•doorwidth : 200cm
•roomtemperature : 20ºC
•airoutlettemperature
1
: speed1-5=35°C
speed6 =40°C
•powersupply :W=230V/E=400V
*Seetableonpage10.
CA
2
S-200
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
200 - 240
79/108/102
23.1
598
4.83
0.38
1.69
-
-
89/118/112
20.0
-
-
0.38
1.69
21.0
32.0
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
835
4.2
30
1170
5.9
38
1350
6.8
41
1745
8.8
46
2035
10.2
50
2305
15.4
53
CA
2
M-200
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
220 - 280
92/121/115
31.6
740
7.12
0.53
2.48
-
-
100/129/123
26.6
-
-
0.53
2.48
28.0
45.5
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
985
4.9
29
1460
7.3
39
1760
8.8
44
2390
12.0
50
2855
14.3
53
3155
21.1
56
CA
2
L-200
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
250 - 330
121/155/151
66.0
1491
10.78
1.34
6.07
-
-
137/171/167
46.6
-
-
1.34
6.07
49.0
75.8
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
2290
11.5
40
3015
15.1
45
3775
18.9
49
4860
24.4
55
5730
28.7
59
6575
44.0
61
CA
2
XL-200
Water
Electric
door height*
weight model F/R/C
max. heating capacity
2
water flow rate
3
water pressure loss, incl. valve
3
max. power, motors
max.current,motors(1phase)
max. power consumption, heating
max.currentconsumption(3phases)
cm
kg
kW
l/h
kPa
kW
A
kW
A
300 - 380
130/164/160
79.9
1676
13.32
2.23
10.0
-
-
146/180/176
46.6
-
-
2.23
10.0
49.0
79.4
Speed 1 2 3 4 5 6
air displacement
heating capacity
noise level at 3 m
m
3
/h
kW
dB(A)
2740
13.8
46
3635
18.2
50
4585
23.0
54
5950
29.9
59
7065
35.5
63
7965
53.3
66
The CA
2
air curtain is as a standard suitable for all water ranges from 45/35 °C to 90/70°C.
1
Dependingonthesituationtheoutlettemperaturevariesinallspeedsbetween20°Cand50°Cmax.
2
Basedonalimitedairoutlettemperatureof50°C.
3
Basedonawaterrangeof60/40°C.